Interruptor Terrae EK6-12/31.5 Altae Tensionis AC Interioris
  • Singula Producti

  • Etiquettae Productarum

Conspectus generalis:

Series EK6-12/31.5, interruptor terrestris interioris, novo consilio praeditus est, a typo ES1 emendatus. Aptus est systematibus electricis 3-12KV, trium phasium et AC 50(60)Hz. Normis GB1985-2004 et IEC129 respondet.

Exemplar: EK6-12/31.5

 

Data technica:

RES UNITAS DATA
Tensio aestimata KV 12
Currentis tolerabilis brevis temporis aestimata KA 31.5
Tempus tolerandi circuitum brevem aestimatum S 4
Currentis brevis circuitus aestimatae KA 80
Currentis sustinendi culminis aestimati KA 80
Tensio sustinenda frequentiae potentiae 1min KV 42
Tensio sustinenda impulsuum fulminis KV 75
Vita mechanica TEMPORA MM

Dimensio:

EK6-1

EK6-2

 

 

UNITATIS: MM

Dimensio

E

F

G

H

D

C

EK6-12/31.5-165

CLXV

75

CLX

565

426

 

EK6-12/31.5-180

CLXXX

75

CLX

595

456

 

EK6-12/31.5-200

ducenti

75

CLX

DCXXXV

496

 

EK6-12/31.5-210

210

75

CLX

DCLV

516

 

EK6-12/31.5-220

220

75

CLX

DCCLXXV

536

 

EK6-12/31.5-230

230

75

CLX

DCXCV

556

96

EK6-12/31.5-250

250

75

CLX

DCCXXXV

596

96

EK6-12/31.5-275

275

75

CLXXXV

DCCCX

DCXLVI

96

Conditio ambiens:

① Altitudo non plus quam mille metra supra mare.
② Temperatura ambientis non altior quam +40°C neque inferior quam -10°C.
③ Humiditas relativa non maior quam 95% in media diurna et non maior quam 90% in media menstrua.
4. Intensitas seismica octo gradus non excedit.

Inquisitio

Si quamlibet quaestionem de pretio vel cooperatione habes, libenter nobis per electronicam epistulam scribe.global@anhelec.comvel sequentem formam inquisitionis utere. Nostri venditores te intra horas XXIV contactabunt. Gratias tibi ago pro interesse tuo in nostris productis.